Welcome
at our official site “ Ukrbudmash Plant Ltd”
TRANSFORMER
OIL TREATEMENT UNIT TYPE UVM
This
document contains protected copyright
information.All
the rights are reserved. Any part of this manual
can not be copied by any of mechanical,
electronic or other means without prior
Manufacturer’s permission.
*Due
to continuous improvement of the plant, certain
parts may differ from the default specification.
1.
APPLICATION
Transformer oil treatment unit UVM type is
designed for degassing,
removing solids,
nitriding and heating transformer oil which
power transformers with voltage up to 1150 kV
are filled in.
Unit
is
used
for heating
oil-filled
electric
units
with
hot
transformer oil,
as well as vacuumizing power transformers.
It is also used in mounting, repairing and
operating
companies
processing
transformer oil.
It
is
necessary
to
provide
degassing
discharge
from station into atmosphere via pipe line while
utilizing
station
in
the
enclosed
premises.
The machine
complies with climatic designer U2
as per
GОSТ
15150-69.
2.
SPECIFICATIONS
2.1
Primary station specifications are stated in the
table
1.
Таble
1
|
Parameters |
Value |
|
1.
Capacity,
m3/h,
:
-
in degassing condition
-
in transmitting condition with
filtration |
1,0
6 |
|
2*.
Processed oil characteristics:
-
oil bulk gas content %
-
мass
moisture content,
g/t
-
filtration fineness,
mcm |
0,1
10
5 |
|
3.
Outlet pressure in processing
condition,
МPа |
0,2 |
|
4.
Oil heater power,
kW |
29 |
|
5.
Set power consumption,
kW |
36 |
|
6.
Three-phase VAC~
50Hz,
V |
380 |
|
7.
Oil temperature in processing
condition,
0С |
50-60 |
|
8.
Limiting oil output temperature in
heating condition,
0С |
60 |
|
9.
Residual pressure in vacuum column
in degassing condition,
Pa |
266 |
|
10.
Dimensions,
mm
-
length
-
height
-
width |
1600
1150
1930 |
|
11.Маss,
kg
|
1100 |
1.
Note
- *
oil metrics:
2.
–
bulk gas content no more than
10,5%
3.
– маss
moisture content no more
0,005% (50г/т)
4.
-
temperature not lower than
00С.