Welcome at our official site
“ Ukrbudmash Plant Ltd”
-
Oil Purification Zeolite Station MCU-4,3
This document contents protected copyright
information.
All therights are reserved.
Any parts of this manual can not be copied by
any of mechanical, electronic or other means
without prior Manufacturer’s written permission.
*Due
to continuous improvement of the plant, certain
parts may differ from the default specification.This
will not reduce performance of the system.
-
1.
APPLICATION
Oil
Purification
Zeolite
Station
MCU-4,3
is
designed
to
remove
solids
and
water
from
insulating
oils,
whose
viscosity
at
temperature
50C
does
not
exceed
70
cSt.
and to lower acidity.
Station
is used for mounting, repairing and operating
high-voltage equipment with voltage up to 1150
kV(power transformers, high-voltage switches etc.)
The
machine complies with number 4 category
placement and climatic design UHL as per GOST
15150-69.
Operational
conditions:
-
ambient temperature
283
to
308К
(+10
to +
35)°С;
-
atmospheric pressure
84
to
106,7
kPа
( 630
to
800
mm.Hg);
-
altitude above sea level
2000
m;
-
ex-proof premises.
2.
SPECIFICATIONS
2.1
Primary station specifications are stated in the
table
1.
Таble
1.
|
№ |
Parameter |
Value |
|
1 |
Capacity,
m3/h:
|
4,3 |
|
2 |
Маximum
oil outlet temperature under heating,
°С |
60 |
|
3 |
Processed oil characteristics
(initial
moisture content
50
g/t):
-
mass moisture content,
g/t
-
filtration fineness,
mcm |
10,0
5 |
|
4 |
Sorbent cartridges block:
-quantity,
pcs.
-sorbent,
type
-zeolite
weight in 2 catridges,
kg |
2
NaA
240 |
|
5 |
Oil heater power,
kW |
29 |
|
6 |
Oil heater specific surface power
kW/cm2
|
1,1 |
|
7 |
Маximum
power consumption,
kW |
32 |
|
8 |
Three-phase VAC~50 Hz,V |
380 |
|
9 |
Dimensions,
mm
Heating and filtration block
-length
-width
-height
Sorbent cartridges block CP-260
-length
-
width
-
height |
1270
700
1500
1200
900
1950 |
|
10 |
Маss,
kg
-
heating and filtration block
-
sorbent cartridges block CP-260 |
300
500 |
3.
DESIGN AND PRINCIPLES OF OPERATION
Station
(see
figure
1)
consists of two self-contained
units:
heating and filtration block
«BNF»
and
sorbent cartridges block CP-260
which are joined
by flexible hoses.
Heating and filtration block
«BNF»
consists of:
-oil
heater
1
-pumping
unit NS-50
-primary
purification cartridge filter FP1
-fine
purification cartridge filter FP2
-complete
control unit KUU;
-piping
system.